12KV 10kA Polymer Surge Arrester

surge arresters

12KV 10kA Polymer Surge Arrester

  • Model YH10W-12

M.V. Polymer Surge Arresters are used to protect transformers and other equipments in station and distribution systems against the damage by atmospheric (especially lightning effects) and operational conditions.
oxides of metals Gapless surge arresters are intended to stop potential harm from occurring in the event of common energy system surges, without affecting the system at normal operation voltage. Due to the non-linear properties of metal-oxide varistors between the voltage and current scales, gapless arresters have this unique feature. When compared to silicon carbide surge arresters, the non-linear feature is significantly greater. 

Contact us

NORMAL SERVICE CONDITIONS

 1.The ambient temperature: -40°C ~+40°C
 2.The altitude above sea level :not exceed 1000-2000m (the altiplano area should be indicated when order)
 3.Earthquake intensity: not higher than 7 degrees;
 4.Maximum wind velocity :less than 35m/s.
 5.The filthy area should be given clear indication.

PRODUCT FEATURE

The most sophisticated over-voltage protection available today is the zinc oxide lightning arrester. Because zinc oxide arrester is the primary resistor disc used in the core component. In contrast to the traditional silicon carbide arrester, this product's prescription significantly enhances the resistor disc's volt-ampere characteristics and boosts its through-current capabilities at over-voltage, resulting in significant local modifications to the arresters' characteristics.

* Rated Voltage(Ur): 3kV – 36kV
* Nominal Discharge Current(In): 5kA or 10kA
* Long Duration Current Impulse: 150A or 250A
* High Current Impulse(Imax): 65kA or 100kA
* Pressure relief capability: 16kA or 20kA
* Creepage distance: ≥31mm/kV
1kjo

PRODUCT parameter

10kA Series

Arrester type

Rated voltage Ur (kV)
Max. continues operating voltage Residual Voltage (kV)
as per IEC as per ANSI/IEEE 1/10 μs Steep current impuse 8/20μs Lightning current impulse 30/60μs Switching current impulse
Uc (kV) MCOV (kV)
Y10W-3/9 3 2.4 2.55 11.3 9 8.9
Y10W-6/18 6 4.8 5.1 20.5 18 16
Y10W-9/27 9 7.2 7.65 31 27 24
Y10W-10/30 10 8.0 9.3 34.1 30 26.6
Y10W-11/33 11 8.8 9.35 38 33 29
Y10W-12/36 12 9.6 10.2 41.5 36 30.6
Y10W-15/45 15 12.0 12.7 52 45 38.3
Y10W-18/54 18 14.4 15.3 62 54 46
Y10W-21/63 21 16.8 17 72.5 63 53.5
Y10W-24/72 24 19.2 19.5 82.5 72 61.2
Y10W-27/81 27 21.6 22 93.2 81 69
Y10W-30/90 30 24.0 24.4 104 90 80
Y10W-33/99 33 26.4 28.0 113.8 99 84.2
Y10W-36/108 36 28.8 29.0 124.2 108 91.8

5kA Series

Arrester type Rated voltage Ur (kV) Max. continues operating voltage Residual Voltage (kV)
as per IEC as per ANSI/IEEE 1/10 μs Steep current impuse 8/20μs Lightning current impulse 30/60μs Switching current impulse
Uc (kV) MCOV (kV)
Y5W-3/9 3 2.4 2.55 11.3 9 8.9
Y5W-6/18 6 4.8 5.1 20.5 18 16
Y5W-9/27 9 7.2 7.65 31 27 24
Y5W-10/30 10 8.0 9.3 34.1 30 26.6
Y5W-11/33 11 8.8 9.35 38 33 29
Y5W-12/36 12 9.6 10.2 41.5 36 30.6
Y5W-15/45 15 12.0 12.7 52 45 38.3
Y5W-18/54 18 14.4 15.3 62 54 46
Y5W-21/63 21 16.8 17 72.5 63 53.5
Y5W-24/72 24 19.2 19.5 82.5 72 61.2
Y5W-27/81 27 21.6 22 93.2 81 69
Y5W-30/90 30 24.0 24.4 104 90 80
Y5W-33/99 33 26.4 28.0 113.8 99 84.2
Y5W-36/108 36 28.8 29.0 124.2 108 91.8