Leave Your Message
12KV 3 Phase Vacuum Circuit Breaker - Indoor High Voltage

Indoor Circuit Breakers

12KV 3 Phase Vacuum Circuit Breaker - Indoor High Voltage

  • Model ZN28-12

ZN28G ZN28A-12 series indoor vacuum circuit breaker is a three _phase AC 50Hz, rated vltage of 12kV indoor swichgear, control and protection for industrial and mining enterprise, power plants and substations, ecrical failis, and for frequent operation place.

Contact us

Overall dimension

gdf

Model description

gfd1

Product Parameter (Specification)

Item

Units

Parameters

Rated voltage

KV

12

Rated current

A

630-3150

Rated short- circuit breaking current

KA

20

31.5

40

Rated short- circuit closing current

KA

50

80

100

Rated dynamic steady electric current(peak)

KA

50

80

100

Rated thermal stability current(RMS)

KA

20

31.5

40

Rated thermal stability time

S

4

The breaking times of rated short circuit breaking current

Times

30 (50)

Open time of CD10 electromagnetic operating mechanism

mS

< 80

Rated operating sequence

 

O-0.3s-CO- 180s-CO

A minute power frequency withstand voltage(RMS)

KV

 The phase 42, section 48

Lightning shock pressure

KV

 The phase 75, section 85

Mechanical life

Times

 10000

 Note: 20KA,31.5KA   t=0.3s t 1= 180s    40KA t=180s t 1= 180s.

product description

Power supply conditions

Within the factory production ZN28G-12 series indoor high voltage vacuum circuit breaker, can be equipped with CT17, CT19 spring mechanism and CD17 electromagnetic mechanism.

Ambient condition

1. Altitude:≤1000m;

2. The ambient temperature: not higher than +40℃. not less than 10℃(-30℃ is permitted storage)

3. Earthquake does not exceed degree 8;

4. Relative humidit: daily average value is not greater than 95%.monthly average is not greater than 90%; air relative humidity on average less than 2210-3Mpa. on average less than 1.810-3Mpa.

5. The surrounding air is not corrosive and flammable gas, steam and other significant plluion;

contact us