Leave Your Message
15KV 600A Single Phase Disconnecting Standard Type Porcelain Isolate Switch

Disconnector Switch

15KV 600A Single Phase Disconnecting Standard Type Porcelain Isolate Switch

  • Model GW9-15/600

a piece of electrical equipment that safely disconnects specific high-voltage electrical network segments when there is no more current flowing through them. It is feasible to reduce the complexity of switching point and transformer substation layouts and do away with costly high-voltage circuit breakers by utilizing isolating switches, either by themselves or in conjunction with high-speed short-circuiting devices.

Contact us

Description

This product is a single phase of a three-phase line phase. It is affordable, easy to use, and has a straightforward construction.

Use environment

1. Altitude: no more than 3000 m
2. The environment temperature: + 50 Degrees Celsius~-50Degrees Celsius
3. no more than 35m/s
4. Cladding ice thickness is no more than 10 mm
5. Use of foul level: Ⅲ,IV class
6.Sunlight intensity:1000W/㎡

Product Parameter

item

Unit

parameter

Rated voltage

kV

10

15

24

Rated working voltage

kV

12

17.5

Rated insulation level

1min frequency withstand voltage (RMS)

kV

To ground42

To ground55

To ground65

kV

Fracture48

fracture65

Fracture79

Lightning impulse withstand voltage (peak)

kV

To ground75

To ground105

To ground125

Fracture85

Fracture120

Fracture145

Rated frequency

HZ

50

Rated current

A

200

400

600

1250

400

630

4s rated short-time withstand current

kA

6.3

12.5

20

31.5

16

20

rated peak withstand current

kA

16

31.5

50

80

40

50

Creepage distance

mM

300

380

Mechanical life

tIMES

2000

2000

2000

Overall dimension

tgdr (1)l20tgdr (2)bl6

contact us