18KV 10kA Polymer Surge Arrester
NORMAL SERVICE CONDITIONS
1.The ambient temperature: -40°C ~+40°C
2.The altitude above sea level :not exceed 1000-2000m (the altiplano area should be indicated when order)
3.Earthquake intensity: not higher than 7 degrees;
4.Maximum wind velocity :less than 35m/s.
5.The filthy area should be given clear indication.
PRODUCT FEATURE
The zinc oxide lightning arrester is the most advanced over-voltage protector in the world. Due to make the resistor disc of core component mainly adopt zinc oxide arrester. Compared with the conventional silicon carbide arrester, this prescription of the product improves greatly the volt-ampere characteristics of the resistor disc and increase through- current capability at over-voltage so as to bring a rad local-changes for the characteristics of the arresters.
* Rated Voltage(Ur): 3kV – 36kV
* Nominal Discharge Current(In): 5kA or 10kA
* Long Duration Current Impulse: 150A or 250A
* High Current Impulse(Imax): 65kA or 100kA
* Pressure relief capability: 16kA or 20kA
* Creepage distance: ≥31mm/kV

PRODUCT parameter
10kA Series
Arrester type |
Rated voltage Ur (kV) |
Max. continues operating voltage | Residual Voltage (kV) | |||
as per IEC | as per ANSI/IEEE | 1/10 μs Steep current impuse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse | ||
Uc (kV) | MCOV (kV) | |||||
Y10W-3/9 | 3 | 2.4 | 2.55 | 11.3 | 9 | 8.9 |
Y10W-6/18 | 6 | 4.8 | 5.1 | 20.5 | 18 | 16 |
Y10W-9/27 | 9 | 7.2 | 7.65 | 31 | 27 | 24 |
Y10W-10/30 | 10 | 8.0 | 9.3 | 34.1 | 30 | 26.6 |
Y10W-11/33 | 11 | 8.8 | 9.35 | 38 | 33 | 29 |
Y10W-12/36 | 12 | 9.6 | 10.2 | 41.5 | 36 | 30.6 |
Y10W-15/45 | 15 | 12.0 | 12.7 | 52 | 45 | 38.3 |
Y10W-18/54 | 18 | 14.4 | 15.3 | 62 | 54 | 46 |
Y10W-21/63 | 21 | 16.8 | 17 | 72.5 | 63 | 53.5 |
Y10W-24/72 | 24 | 19.2 | 19.5 | 82.5 | 72 | 61.2 |
Y10W-27/81 | 27 | 21.6 | 22 | 93.2 | 81 | 69 |
Y10W-30/90 | 30 | 24.0 | 24.4 | 104 | 90 | 80 |
Y10W-33/99 | 33 | 26.4 | 28.0 | 113.8 | 99 | 84.2 |
Y10W-36/108 | 36 | 28.8 | 29.0 | 124.2 | 108 | 91.8 |
5kA Series
Arrester type | Rated voltage Ur (kV) | Max. continues operating voltage | Residual Voltage (kV) | |||
as per IEC | as per ANSI/IEEE | 1/10 μs Steep current impuse | 8/20μs Lightning current impulse | 30/60μs Switching current impulse | ||
Uc (kV) | MCOV (kV) | |||||
Y5W-3/9 | 3 | 2.4 | 2.55 | 11.3 | 9 | 8.9 |
Y5W-6/18 | 6 | 4.8 | 5.1 | 20.5 | 18 | 16 |
Y5W-9/27 | 9 | 7.2 | 7.65 | 31 | 27 | 24 |
Y5W-10/30 | 10 | 8.0 | 9.3 | 34.1 | 30 | 26.6 |
Y5W-11/33 | 11 | 8.8 | 9.35 | 38 | 33 | 29 |
Y5W-12/36 | 12 | 9.6 | 10.2 | 41.5 | 36 | 30.6 |
Y5W-15/45 | 15 | 12.0 | 12.7 | 52 | 45 | 38.3 |
Y5W-18/54 | 18 | 14.4 | 15.3 | 62 | 54 | 46 |
Y5W-21/63 | 21 | 16.8 | 17 | 72.5 | 63 | 53.5 |
Y5W-24/72 | 24 | 19.2 | 19.5 | 82.5 | 72 | 61.2 |
Y5W-27/81 | 27 | 21.6 | 22 | 93.2 | 81 | 69 |
Y5W-30/90 | 30 | 24.0 | 24.4 | 104 | 90 | 80 |
Y5W-33/99 | 33 | 26.4 | 28.0 | 113.8 | 99 | 84.2 |
Y5W-36/108 | 36 | 28.8 | 29.0 | 124.2 | 108 | 91.8 |