36KV 10kA Polymer Lightning Arrester

surge arresters

36KV 10kA Polymer Lightning Arrester

  • Model YH10W-36

M.V. Polymer Lightning Arresters are used to protect transformers and other equipments in station and distribution systems against the damage by atmospheric (especially lightning effects) and operational conditions.
Oxides of metals Without gaps, the purpose of lightning arresters is to shield energy systems from potential harm during regular surges, without compromising normal operating voltage. The unique quality of gapless arresters stems from the non-linear properties of metal-oxide varistors in the voltage and current scales. The non-linear characteristic is significantly greater than that of silicon carbide lightning arresters.

Contact us

NORMAL SERVICE CONDITIONS

 1.The ambient temperature: -40°C ~+40°C
 2.The altitude above sea level :not exceed 1000-2000m (the altiplano area should be indicated when order)
 3.Earthquake intensity: not higher than 7 degrees;
 4.Maximum wind velocity :less than 35m/s.
 5.The filthy area should be given clear indication.

PRODUCT FEATURE

The zinc oxide lightning arrester is the most advanced over-voltage protector in the world. Due to make the resistor disc of core component mainly adopt zinc oxide arrester. Compared with the conventional silicon carbide arrester, this   prescription of the product improves greatly the volt-ampere characteristics of the resistor disc and increase through- current capability at over-voltage so as to bring a rad local-changes for the characteristics of the arresters.

* Rated Voltage(Ur): 3kV – 36kV
* Nominal Discharge Current(In): 5kA or 10kA
* Long Duration Current Impulse: 150A or 250A
* High Current Impulse(Imax): 65kA or 100kA
* Pressure relief capability: 16kA or 20kA
* Creepage distance: ≥31mm/kV
1174

PRODUCT parameter

10kA Series

Arrester type

Rated voltage Ur (kV)
Max. continues operating voltage Residual Voltage (kV)
as per IEC as per ANSI/IEEE 1/10 μs Steep current impuse 8/20μs Lightning current impulse 30/60μs Switching current impulse
Uc (kV) MCOV (kV)
Y10W-3/9 3 2.4 2.55 11.3 9 8.9
Y10W-6/18 6 4.8 5.1 20.5 18 16
Y10W-9/27 9 7.2 7.65 31 27 24
Y10W-10/30 10 8.0 9.3 34.1 30 26.6
Y10W-11/33 11 8.8 9.35 38 33 29
Y10W-12/36 12 9.6 10.2 41.5 36 30.6
Y10W-15/45 15 12.0 12.7 52 45 38.3
Y10W-18/54 18 14.4 15.3 62 54 46
Y10W-21/63 21 16.8 17 72.5 63 53.5
Y10W-24/72 24 19.2 19.5 82.5 72 61.2
Y10W-27/81 27 21.6 22 93.2 81 69
Y10W-30/90 30 24.0 24.4 104 90 80
Y10W-33/99 33 26.4 28.0 113.8 99 84.2
Y10W-36/108 36 28.8 29.0 124.2 108 91.8

5kA Series

Arrester type Rated voltage Ur (kV) Max. continues operating voltage Residual Voltage (kV)
as per IEC as per ANSI/IEEE 1/10 μs Steep current impuse 8/20μs Lightning current impulse 30/60μs Switching current impulse
Uc (kV) MCOV (kV)
Y5W-3/9 3 2.4 2.55 11.3 9 8.9
Y5W-6/18 6 4.8 5.1 20.5 18 16
Y5W-9/27 9 7.2 7.65 31 27 24
Y5W-10/30 10 8.0 9.3 34.1 30 26.6
Y5W-11/33 11 8.8 9.35 38 33 29
Y5W-12/36 12 9.6 10.2 41.5 36 30.6
Y5W-15/45 15 12.0 12.7 52 45 38.3
Y5W-18/54 18 14.4 15.3 62 54 46
Y5W-21/63 21 16.8 17 72.5 63 53.5
Y5W-24/72 24 19.2 19.5 82.5 72 61.2
Y5W-27/81 27 21.6 22 93.2 81 69
Y5W-30/90 30 24.0 24.4 104 90 80
Y5W-33/99 33 26.4 28.0 113.8 99 84.2
Y5W-36/108 36 28.8 29.0 124.2 108 91.8