01
400A Overhead Service Low Voltage 415V Pole Mounted Cutout
Product Introduction
This version can be pole, cross arm or wall mounted, its compact size allowing optimized arrangements resulting in less obtrusive installations.
Mechanical terminals with shear head bolts replace the studs usually associated with this type of cutout, eliminating the need for additional connecting lugs and specialized tools to ensure a simple, safe and effective joint.
The terminals will accept solid or stranded aluminium and solid copper conductors in the range 70 to 300mm². An adaptor is available for 25/35mm² copper or aluminium conductors.
The fuse carrier accepts J type fuse links to BS88 rated up to 400A.
With the PVC cable sealing grommets in place, the cutout is IP43 rated and has been designed to fully comply with the performance requirements specified in BS7656:1993 for LV pole mounting fuses.
The enclosure is moulded in high performance, glass reinforced polyester, renowned and proven worldwide.
Product Parameter (Specification)
No. |
Description |
Value |
1 |
Standards Referred |
ESI12.20, BS88 Part1: 1975, IEC 947-3 |
2 |
Rated Voltage (V) |
415V |
3 |
Rated Current (A) |
400A |
4 |
Size: Height (mm) Width (mm) Depth (mm) |
≤300 ≤400 ≤120 |
5 |
Contacts Material |
Copper, Bright Tinned Copper or Copper Alloy Silver Plated |
6 |
Housing Material |
Glass Reinforced Polyester or Nylon |
7 |
Fixing Centres for J-Type Fuse |
82.5mm |
Product Feature and Application
Each fused cut-out has fuse contacts and cable terminal plates which are manufactured from copper and bright tinned. These plates incorporated M12 captive studs with nuts and washers for the reception of cable sockets (lugs) up to 300 mm² (*compression type only at 300 mm²) with copper or aluminium conductors.
For ease of mounting to either a wall or a wooden pole, the fused cutout is supplied with an M12 coach screw.
For cross-arm type mounting the fused cutout can be supplied with an M12 nut, bolt and washer.
Product Details