1.Highest voltage for equipment can be up to 24 kV.
2.No maintenance is required
3.Protection against: IOV
4.Only 1 product per pole is required
  • MLPD24-C
  • Jecsany
Quantity:

Specification

1.Highest voltage for equipment can be up to 24 kV.

2.No maintenance is required

3.Protection against: IOV

4.Only 1 product per pole is required

5.Products are installed with phase alternation (А -> B -> C)

6.Definitely great use and the highest possible reliability

7.Line Protection Device has been designed to ensure the most effective protection from indirect strokes. This device is able to perform as highly effective lightning protection system, providing secure power network operation in 80% of such issues.

8.In order to protect sensitive equipment, such as pole-mounted transformers (PMT), conventional metal oxide surge arresters still must be used


Operational Principle

1.Ensuring a high ability to discharge excessive energy of an overvoltage in the surrounding atmosphere

2.The induced overvoltage will create an electrical power arc between the terminal electrode of a MLPD and the conductor clamp on a line. First, the arc will be divided into a series of small arcs by a series of discharge chambers, and then quickly extinguished when the oscillating current of the grid exceeds zero.


Parameters

Description

Unit

Value

Electrical line parameters



Highest voltage for equipment ⑴ 

kV

24

Maximum prospective fault current

kA

1,5

External air gap

mm

60±10

50% flashover voltage

kV

140

Power frequency withstand voltage ⑵

kV (wet/dry)

30/40

Lightning parameters



Lightning discharge capability  (200 μs) ⑶ 

C

2.4

High current impulse (4/10 μs)

kA

65

Maximum quenching lightning current,

kA

3 (1/50µs)

Minimum withstand amount of operations


10

General Parameters



Additional power losses on the line

%

0

Average expected lifespan

years

30

UV resistance ⑷ 

h

1000

Weight

kg

0.43

Maintenance


1 visual verification per year


⑴ According to IEC 60038, ⑵ According to IEC 60071-1, ⑶ According to  IEC 60099-8, ⑷ According to ISO 4892-2, method A, IEC 62217


Size

图片1

Installation

Pin/post/pin-post 

Line Protection Device Line Protection Device
Line Protection Device Line Protection Device
Line Protection Device


Tension insulation

Tension insulation Tension insulation


Horizontal post insulation

图片9


Product Inquiry

PRODUCTS

CONTACT US

ADD:      1906, Haiyun Building, No.70, Tianjian Lane, 
                Shounan Street, Yinzhou District, Ningbo,
                Zhejiang,  China (Mainland) 
PHONE:  +86-13065600656
E-MAIL:   jecsany@163.com   
                Jason@jecsany.com 
© 2019 Ningbo Jecsany Electrical Equipment Co., Ltd. All Rights Reserved.