jecsany@163.com      +86-13065600656    
You are here: Home » Products » Line Protection Device » MLPD35-D Multi-chamber Arc Blowing Type Line Protection Device 35KV
PRODUCT DETAIL

MLPD35-D Multi-chamber Arc Blowing Type Line Protection Device 35KV

Share to:
1.Highest voltage for equipment can be up to 40.5 kV.
2.Maximum prospective fault current 5.0 kA
3.Lightning discharge capability 2.8 C
4.Installation 1, 2 or 3 pcs per pole
  • MLPD35-D
  • Jecsany
Quantity:

Specification

1.Highest voltage for equipment can be up to 40.5 kV.

2.Maximum prospective fault current 5.0 kA

3.Lightning discharge capability 2.8 C

4.Installation 1, 2 or 3 pcs per pole

5.Protects from Direct Lightning Strike (DLS)

6.Protects from Back Flashover (BFO)

7.No maintenance is required



Usage and Expected Lifespan

1.This device is designed to protect power supply networks from the consequences of either direct lightning strikes or induced overvoltages. Indented to be installed along the protected line, it works perfectly on distribution lines with the highest voltage of equipment up to 40.5 kV.

2.The expected lifespan is up to decades.



Operational Principle

MLPD35-D can easily be adapted to any cross-arm or pole configuration. This is possible due to different attaching solutions and accessories available.



Parameters

Description

Unit

Value

Electrical line parameters



Highest voltage for equipment ⑴ 

kV

40.5

Maximum prospective fault current

kA

5

External air gap

mm

110-180

50% flashover voltage

kV

230

Power frequency withstand voltage ⑵

kV (wet/dry)

65/80

Lightning parameters



Lightning discharge capability  (200 μs) ⑶ 

C

2.8

High current impulse (4/10 μs)

kA

65

Maximum quenching lightning current

kA

20 (8/50µs)

Minimum withstand amount of operations


10

General Parameters



Additional power losses on the line

%

0

Average expected lifespan

years

30

UV resistance ⑷ 

h

1000

Weight

kg

5.6

Maintenance


1 visual verification per year


⑴ According to IEC 60038, ⑵ According to IEC 60071-1, ⑶ According to  IEC 60099-8, ⑷ According to ISO 4892-2, method A, IEC 62217


Size

size


Installation

Pin/post/pin-post 

Installation1 Installation2
Installation3 Installation4


Suspension insulation

Suspension insulation1 Suspension insulation


Tension insulation

Tension insulation Tension insulation
Tension insulation



Horizontal post insulation

Horizontal post insulation

Product Inquiry

PRODUCTS

CONTACT US

ADD:      1906, Haiyun Building, No.70, Tianjian Lane, 
                Shounan Street, Yinzhou District, Ningbo,
                Zhejiang,  China (Mainland) 
PHONE:  +86-13065600656
E-MAIL:   jecsany@163.com   