Leave Your Message
Auto Recloser  with Intelligent Controller

Outdoor Circuit Breakers

Auto Recloser with Intelligent Controller

  • Model ZW43R-24

The circuit breaker's auto recloser with intelligent controller uses solid sealing technology, and silicone rubber sleeves are used for external insulation. It has a long lifespan and great dependability. The operating mechanism of the auto recloser can be either an advanced permanent magnet mechanism or a miniature, highly reliable spring mechanism. In order to achieve four remote control capabilities and power distribution automation, it can also be fitted with intelligent controllers and isolating switches. It can also be utilized as a sectioner or recloser.

Contact us

General

Auto Recloser  with Intelligent Controller ZW43R-24 Series outdoor high voltage vacuum circuit breaker is rated voltage 24kV, three phase AC 50Hz outdoor distribution equipment. Mainly used for breaking, closing power system load current, overload current and short-circuit current. Applicable to substations and power distribution in industrial and mining enterprises for protection and control purposes, and frequent operation place for rural power grids.

Service environment conditions

a) Ambient Air Temperature:  +45ºC ~ -45ºC
b) Humidity: Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level (Maximum installation altitude): not more than 2500 meters.
d) Ambient air should be not apparently polluted by corrosive and flammable gas, vapor etc.
e) The wind speed is not greater than 35m/s.
f ) Anti-contamination level for grade IV
g) The earthquake intensity does not exceed 8 degrees.

Product Parameter

No. Item Unit Parameters
1 Rated voltage KV 24
2 Rated frequency Hz 50/60
3 Rated current A 630/1250
4 Rated short-circuit breaking current kA 20/25
5 Rated peak value withstand current(peak) kA 50/63
6 Rated short time withstand current kA 20/25
7 Rated short-circuit closing current (peak) kA 50/63
8 Mechanical life TIMES 10000
9 Rated short-circuit breaking current breaking number TIMES 30
10 Power frequency withstand voltages (1 min), wet/dry: inter-phase, earth, fracture KV 65/79
11 Lightning impulse withstand voltage (peak) inter-phase ,earth, fracture KV 125/145
12 Rated operate sequence   O-0.3-CO-180S-CO
13 Secondary circuit 1min power frequency voltages KV 2