Enclosed Switchgear: Efficient Electrical Circuit Management
Product description
TECHNICAL PARAMETER
|
Rated voltage |
kV |
12 |
24 |
|
|
BIL |
common value |
kV |
75 |
125 |
|
|
across the isolating distance |
|
85 |
145 |
|
AC withstand voltage |
common value |
kV |
28 1) |
50 |
|
|
across the isolating distance |
|
32 1) |
60 |
|
Rated frequency |
Hz |
50/60 |
50/60 |
|
|
Rated current |
busbar |
A |
630/1250 |
630/1250 |
|
|
feeder |
A |
630/800/12504) |
630/1250 4) |
|
Rated short-time withstand current |
main circuit |
kA |
25 |
20 |
|
|
earthing circuit |
kA |
25 |
20 |
|
Rated peak withstand current |
kA |
65 |
50 |
|
|
Rated duration of short circuit |
s |
1 |
1 |
|
|
Arc-fault current, 1s |
kA |
20 |
20 |
|
|
Degree of protection, enclosure |
|
IP2XC |
IP2XC |
|
|
Degree of protection, partitions |
|
IP2X |
IP2X |
|
|
Ambient temperature |
maximum value |
[ºC] |
40 |
40 |
|
|
maximum value of 24 h-mean |
|
+35 |
35 |
|
|
minimum value |
|
-5 3) |
-5 3) |
|
Altitude above sea level |
[m] |
<1000 2) |
<1000 2) |
|
Product features
- Enhanced Safety: Enclosed design minimizes exposure to live parts, reducing electrical shock risks; built-in protection mechanisms (e.g., arc fault containment) enhance operational safety.
- Reliable Performance: High-quality components ensure stable current control and fault interruption, suitable for continuous operation in harsh industrial environments.
- Flexible Configuration: Modular design allows customization based on voltage levels, load capacities, and application needs (e.g., indoor/outdoor installation).
- Easy Maintenance: Accessible compartments and standardized parts simplify inspection, repair, and component replacement, reducing downtime.
- Smart Integration: Modern switchgear supports remote monitoring and control via digital interfaces, enabling real-time data analysis and predictive maintenance for improved system efficiency.
Packaging
|
Packaging Details |
Wooden Box |
|
Port |
Ningbo Port, Shanghai Port |

About US: