01
High Voltage Limit Current Fuse
Conditions for normal use
When the High Voltage Limit Current Fuse is in normal use in the transformer oil, the maximum environment temperature is less than 100℃
Technical Parameter
Type |
Rated Voltage (KV) |
Max Working Voltage (KV) |
Fuse Rated Current (KA) |
Rated Current of Fuse (A) |
OKG |
10 |
12 |
125 |
10, 16, 20, 30, 31.5, 45, 50, 63, 80, 100, 125 |
200 |
160, 200 |
Main Technical characteristics
Oil HT (RMU FUSE) for protection oil-immersed type transformer, Diameter of Fuse: 63x254mm
1. The Limit Current Fuse can break any problem current between the minimum break current (2.5-5) In to rated break current 50kA.
2. The upper section above the minimum break current is broken line. Details see chart 3 for the fuse time-current property.
3. Chart 2 is for limit current property.
4. Chart 1 is for the external structure and installation dimensions.

Package Info
Carton Size: 28*22*15.5cm
QTY: 6pcs/CTN
Weight: 11.8KG