Multi-chamber Arc Blowing Type 10KV Line Protection Device
Products

Multi-chamber Arc Blowing Type 10KV Line Protection Device

  • Model MLPD10-I

The multi-cavity arc blowing lightning protection device in the overhead line is characterized in that no special grounding is required, the power frequency freewheeling current can be cut off, the failure rate is low, and the service life is long. The application of the multi-cavity arc blowing lightning protection device plays a key role in the safe and stable operation of the wind farm, and is of great significance to the line operation and maintenance in the wind power aftermarket.

Contact us

Specification

Highest voltage for equipment can be up to 13 kV.
Protects from Induced Overvoltage
No maintenance is required
No special grounding required
Protection against: IOV
Only 1 product per pole is required
Products are installed with phase alternation (А -> B -> C)
Definitely great use and the highest possible reliability
Line Protection Device has been designed to ensure the most effective protection from indirect strokes. This device is able to perform as highly effective lightning protection system, providing secure power network operation in 80% of such issues.
In order to protect sensitive equipment, such as pole-mounted transformers (PMT), conventional metal oxide surge arresters still must be used

Operational Principle

Ensuring a high ability to discharge excessive energy of an overvoltage in the surrounding atmosphere
The induced overvoltage will create an electrical power arc between the terminal electrode of a MLPD and the conductor clamp on a line. First, the arc will be divided into a series of small arcs by a series of discharge chambers, and then quickly extinguished when the oscillating current of the grid exceeds zero.
Make full use of the grounding resistance between two towers, each tower only needs to install one product
It is used for the protection of overhead line induced lightning overvoltage, which is more cost-effective than traditional solutions.

Product Parameter

Description

Unit

Value

Electrical line parameters

 

 

Highest voltage for equipment ⑴ 

kV

13

Maximum prospective fault current

kA

1,5

External air gap

mm

50±10

50% flashover voltage

kV

85

Power frequency withstand voltage ⑵

kV (wet/dry)

20/30

Lightning parameters

 

 

Lightning discharge capability  (200 μs) ⑶ 

C

1.0

High current impulse (4/10 μs)

kA

65

Nominal discharge current

kA

20

General Parameters

 

 

Additional power losses on the line

%

0

Average expected lifespan

years

20

UV resistance ⑷ 

h

1000

Weight

kg

1.0

Maintenance

 

1 visual verification per year

⑴ According to IEC 60038, ⑵ According to IEC 60071-1, ⑶ According to  IEC 60099-8, ⑷ According to ISO 4892-2, method A, IEC 62217