Leave Your Message
Multi-chamber Arc Blowing Type 35KV Line Protection Device
Products

Multi-chamber Arc Blowing Type 35KV Line Protection Device

  • Model MLPD35-D

The multi-cavity arc blowing lightning protection device in the overhead line is characterized in that no special grounding is required, the power frequency freewheeling current can be cut off, the failure rate is low, and the service life is long. The application of the multi-cavity arc blowing lightning protection device plays a key role in the safe and stable operation of the wind farm, and is of great significance to the line operation and maintenance in the wind power aftermarket.

Contact us

Specification

Highest voltage for equipment can be up to 40.5 kV.
Maximum prospective fault current 5.0 kA
Lightning discharge capability 2.8 C
Installation 1, 2 or 3 pcs per pole
Protects from Direct Lightning Strike (DLS)
Protects from Back Flashover (BFO)
No maintenance is required

Specification

Highest voltage for equipment can be up to 40.5 kV.
Maximum prospective fault current 5.0 kA
Lightning discharge capability 2.8 C
Installation 1, 2 or 3 pcs per pole
Protects from Direct Lightning Strike (DLS)
Protects from Back Flashover (BFO)
No maintenance is required

Operational Principle

MLPD35-D can easily be adapted to any cross-arm or pole configuration. This is possible due to different attaching solutions and accessories available.

Product Parameter

Description

Unit

Value

Electrical line parameters

 

 

Highest voltage for equipment ⑴ 

kV

40.5

Maximum prospective fault current

kA

5

External air gap

mm

110-180

50% flashover voltage

kV

230

Power frequency withstand voltage ⑵

kV (wet/dry)

65/80

Lightning parameters

 

 

Lightning discharge capability  (200 μs) ⑶ 

C

2.8

High current impulse (4/10 μs)

kA

65

Maximum quenching lightning current,

kA

20 (8/50µs)

Minimum withstand amount of operations

 

10

General Parameters

 

 

Additional power losses on the line

%

0

Average expected lifespan

years

30

UV resistance ⑷ 

h

1000

Weight

kg

5.6

Maintenance

 

1 visual verification per year

⑴ According to IEC 60038, ⑵ According to IEC 60071-1, ⑶ According to  IEC 60099-8, ⑷ According to ISO 4892-2, method A, IEC 62217

35KV-1

Installation

ouliins (1)ins (2)ins (3)ins (4)

contact us