Leave Your Message

Outdoor 35kV Polymer Fuse Cutout

  • Model F35100C1080

Fuse cutouts provide the primary function of protecting your system's wires and the many devices connected to them, including transformers and capacitor banks. By using their maximal interrupting capability, fuse cuts offer dependable protection against intermediate faults, high faults, and low-level overloads that simply melt the fuse link.

Contact us

Principle and Function of Fuse Cut Out

The insulating support, the dynamic and static contacts, and the fuse tube make up the three components of the high-voltage drop-out fuse. The fuse tube is made consisting of an outside phenolic paper tube or epoxy glass fiber cloth tube and an interior arc suppression tube. The static contacts are mounted at both ends of the insulating support.
Drop-out fuses are suitable for power systems with a frequency of 50/60Hz and a rated voltage of 35KV and below, and are installed on the high-voltage side of distribution transformers or on the main lines of distribution. The main function is where the protection performance is not high, it can be used in conjunction with the isolating switch to replace the automatic air switch; it can also be used in conjunction with the load switch to replace the expensive circuit breaker. It also has short circuit protection, overload and isolation circuits.

Product Parameter

Type

Unit

F35100C1080

F35200C1080

Rated Voltage

KV

35

35

Rated Current

A

100

200

Rated Short-circuit Breaking Current

KA

8

8

Impulse Withstand Voltage (BIL)

KV

170

170

Power Frequency withstand Voltage

KV

80

80

Creepage Distance

mM

1080

1080

Weight

kG

6

6.5

Applicable Standard

IEC 60282-2

IEC 60282-2

Package Size

cM

62.5*30.5*39=3pcs

62.5*30.5*39=3pcs