Product Parameter (Specification)
|
0 |
ltem |
Units |
Technical parameters |
||
|
1 |
Rated voltage |
KV |
12 |
||
|
2 |
Rated short-duration power frequency withstand voltage |
|
42/48(Interphase,ground/fracture) |
||
|
3 |
Rated lightning impulse withstand voltage |
|
42/48(Interphase,ground/fracture) |
||
|
4 |
Rated frequency |
Hz |
50 |
|
|
|
5 |
Rated current |
A |
630 1250 |
63012501600200025003150 |
63012501600200025003150 |
|
6 |
Rated short-circuit breaking current |
KA |
20/25 |
31.5 |
40 |
|
7 |
Rated short-time withstand voltage |
|
20/25 |
31.5 |
40 |
|
8 |
Rated short circuit duration |
S |
4 |
|
|
|
9 |
Rated peak withstand current |
KA |
50/63 |
80 |
100 |
|
10 |
Rated short circuit closing current |
|
50/63 |
80 |
100 |
|
11 |
Secondary circuit power frequency withstand voltage(1min) |
|
2000 |
||
|
12 |
Rated single /back to back capacitor group breaking current |
A |
630/400(40kA:800/400) |
||
|
13 |
Rated capacitor bank closing current |
|
12.5(frequency is not greater than) |
||
|
14 |
Mechanical life |
KA |
20000 |
||
|
15 |
Rated current breaking times(electrical life) |
|
20000 |
||
|
16 |
Rated short circuit current breaking times |
times |
50(40KA≤30) |
||
|
17 |
Dynamic and static contacts allow wear cumulative thickness |
mm |
3 |
||
|
18 |
Energy storage time |
S |
≤10 |
||
|
19 |
Contact opening distance |
mm |
11±1 |
||
|
20 |
overtravel |
|
3.5±0.5 |
||
|
21 |
Contact closing bounce time |
ms |
≤2(40KA≤3) |
||
|
22 |
Three-phase split/closed period |
|
≤2 |
||
|
23 |
Average opening speed (contacts are separated by-8mm) |
m/s |
1.2±0.2 |
||
|
24 |
Main conductive loop resistance |
|
0.6±0.2 |
||
|
25 |
Main conductive loop resistance |
μΩ |
≤50(630A)=45(1250A) |
||
|
26 |
Rated operation sequence |
|
0-0.3s-Co-180s-Co |
||

Product features
● Excellent breaking performance - Vacuum interrupter ensures no reignition or current chopping
● Extra-long service life - Up to 30,000 mechanical operations and 10,000 electrical operations
● Intelligent monitoring - Optional condition monitoring module for real-time parameters tracking
● Modular design - Easy installation and maintenance, compatible with variousswitchgears
Packaging
Normal package, Packed in Roll, Plastic film winding, Standard export carton, Or based on your demands.