Model:MLPD24-C
The Multi-chamber Arc Blowing Type 24KV Line Protection Devicein the overhead line is characterized in that no special grounding is required, the power frequency freewheeling current can be cut off, the failure rate is low, and the service life is long. The application of the multi-cavity arc blowing lightning protection device plays a key role in the safe and stable operation of the wind farm, and is of great significance to the line operation and maintenance in the wind power aftermarket.
Multi-chamber Arc Blowing Type 24KV Line Protection Device
The multi-cavity arc blowing lightning protection device in the overhead line is characterized in that no special grounding is required, the power frequency freewheeling current can be cut off, the failure rate is low, and the service life is long. The application of the multi-cavity arc blowing lightning protection device plays a key role in the safe and stable operation of the wind farm, and is of great significance to the line operation and maintenance in the wind power aftermarket.
Specification
1.Highest voltage for equipment can be up to 24 kV.
Operational Principle
1.Ensuring a high ability to discharge excessive energy of an overvoltage in the surrounding atmosphere
Product Parameter (Specification)
Description | Unit | Value. |
Electrical line parameters |
|
|
Highest voltage for equipment ⑴ |
kV | 24 |
Maximum prospective fault current | kA | 1,5 |
External air gap | mm | 60±10 |
50% flashover voltage | KV | 140 |
Power frequency withstand voltage ⑵ | kV (wet/dry) | 30/40 |
Lightning parameters |
|
|
Lightning discharge capability (200 μs) ⑶ |
C | 1.0 |
High current impulse (4/10 μs) | KA | 65 |
Maximum quenching lightning current, | kA |
10 |
Minimum withstand amount of operations |
|
|
General Parameters |
|
|
Additional power losses on the line | % | 0 |
Average expected lifespan |
years | 30 |
UV resistance ⑷ |
h |
1000 |
Weight |
kg |
0.43 |
Maintenance |
|
1 visual verification per year |
⑴ According to IEC 60038, ⑵ According to IEC 60071-1, ⑶ According to IEC 60099-8, ⑷ According to ISO 4892-2, method A, IEC 62217
Size
Installation
Pin/post/pin-post
Tension insulation
Horizontal post insulation