Model:GW9-27/600
An electrical device for the reliable disconnection of certain sections of a high-voltage electrical network when there is no current in them. The use of isolating switches (either alone or in combination with high-speed short-circuiting devices) makes it possible to simplify the arrangement of switching points and transformer substations and to eliminate expensive high-voltage circuit breakers.
This product is a single phase of the three-phase line phase, with simple structure, economical and convenient to use.
Product use environmental conditions
1. Altitude: no more than 3000 m
2. The environment temperature: + 50 Degrees Celsius~-50Degrees Celsius
3. no more than 35m/s
4. Cladding ice thickness is no more than 10 mm
5. Use of foul level: Ⅲ,IV class
6.Sunlight intensity:1000W/㎡
Product parameters
item | Unit | parameter | ||
Rated voltage | kV | 27 | ||
Max. Operating voltage | kV | 29 | ||
Rated insulation level | 1min frequency withstand voltage (RMS) | kV | 42 | |
kV | 48 | |||
Lightning impulse withstand voltage (peak) | kv | 125 | ||
Rated frequency | Hz | 50/60 | ||
Rated current | A | 600 | ||
4s rated short-time withstand current | kA | 25kA | ||
Creepage distance | mm | 550 |
Overall dimension
Product details